{ Introduction of 4 methods to configure the access control system to release all door locks in fire alarm event }

AR-727-CM-IO-0804M Built-in Fire Alarm Auto Release Door Open Application

 

The chart introduces 4 methods to configure the access control system to release all door locks in fire alarm event
MethodMain ModelConnected DevicesSettingRemark
1Gateway TCP/IP to RS485 Converter
(AR-727-CM-IO-0804M)
IP-based controller
(include Multi-door controller)
AR727CM-IO accept the command from any one AR727CMAR-727-CM-IO is built-in the function that support all methods
AR727CM-IO accept the command from the specified AR727CM
2Remote AR-727-CM-IO CH1/CH2 RS485 readersAR727CM-IO accept the command from any one AR727CM-
AR727CM-IO accept the command from the specified AR727CM
3CH1/CH2 RS485 readerRelease the door lock of all readers-
Release the door lock of specified reader
4Multi-Door Controller
(AR-716-E18/ AR-716-E16)
CH1/CH2 RS485 readerRelease the door lock of all readersRelease all doors via Option setting of Remote Control
Release the door lock of specified reader

 


 

Introduction of releasing all door locks in fire alarm event (1)- IP-based controller & Multi-door controller through AR-727CM-IO

Enterprise E Series TCP/IP Controller support UDP release all door locks through AR-727CM-IO, connect fire detector central controller to Fire alarm DI0 input of TCP/IP controller or Multi-door controller

  1. AR-727-CM-IO-0804M needs to enable the “Fire Alarm (DI0) Open Doors” function
    (A) Each TCP/IP Controller shall be set Secondary DNS Server to UDP release all door locks function on the parameter setting page of browser
    (B) Specify the only source: Enter the specified IP address of AR-727-CM-IO-0804M IP
  2. Open any sources: Enter 0.0.0.0

The above two settings can be set via WEB Setting edit page on broswer, the default IP is 192.168.1.127

* To support UDP releasing all door locks function, the converter AR-727-CM-IO-0804M shall be updated with one special firmware APX727i3___VXXXX 8I4O XXXXXX UDP FireMessage.STM

 

 


 

Introduction of releasing all door locks in fire alarm event (2)- Remote AR-727-CM-IO CH1/CH2 RS485 readers

Network server AR-727-CM-IO-0804M is built-in DI0 input that can be connected to fire alarm detector; all controllers connected under the same network can be released door locks via UDP broadcast method; the network controller can also be set to accept any or only one signal of network server to release door lock.

 

 


 

Introduction of releasing all door locks in fire alarm event (3)- CH1/CH2 RS485 Readers under AR-727-CM-IO

AR-727-CM-IO-0804M is built-in fire detection input (DI0); When the fire alarm is triggered, all door locks of CH1/CH2 RS-485 controllers under AR-727-CM-IO will be released for user to escape.

AR-727-CM-IO-0804M needs to enable the “Fire Alarm (DI0) Open Doors” function

(The function can be set on browser, default IP address is 192.168.1.127)

 

 

 


 

Introduction of releasing all door locks in fire alarm event (4) –Control CH1/CH2 RS485 Reader under Multi-door controller

SOYAL Multi-door controller AR-716-E16 and AR-716-E18 are built-in fire detection input. Only connect the input to fire detector central controller and then once the fire alarm is triggered, all door locks of RS-485 controllers under Multi-door control panel will be released for user to escape.

(Enable the function via parameter setting page on 701Server)

 

 