AR-727-CM-IO-0804M Built-in Fire Alarm Auto Release Door Open Application
The chart introduces 4 methods to configure the access control system to release all door locks in fire alarm event | ||||
Method | Main Model | Connected Devices | Setting | Remark |
1 | Gateway TCP/IP to RS485 Converter (AR-727-CM-IO-0804M) | IP-based controller (include Multi-door controller) | AR727CM-IO accept the command from any one AR727CM | AR-727-CM-IO is built-in the function that support all methods |
AR727CM-IO accept the command from the specified AR727CM | ||||
2 | Remote AR-727-CM-IO CH1/CH2 RS485 readers | AR727CM-IO accept the command from any one AR727CM | - | |
AR727CM-IO accept the command from the specified AR727CM | ||||
3 | CH1/CH2 RS485 reader | Release the door lock of all readers | - | |
Release the door lock of specified reader | ||||
4 | Multi-Door Controller (AR-716-E18/ AR-716-E16) | CH1/CH2 RS485 reader | Release the door lock of all readers | Release all doors via Option setting of Remote Control |
Release the door lock of specified reader |
Introduction of releasing all door locks in fire alarm event (1)- IP-based controller & Multi-door controller through AR-727CM-IO
Enterprise E Series TCP/IP Controller support UDP release all door locks through AR-727CM-IO, connect fire detector central controller to Fire alarm DI0 input of TCP/IP controller or Multi-door controller
The above two settings can be set via WEB Setting edit page on broswer, the default IP is 192.168.1.127
* To support UDP releasing all door locks function, the converter AR-727-CM-IO-0804M shall be updated with one special firmware APX727i3___VXXXX 8I4O XXXXXX UDP FireMessage.STM
Introduction of releasing all door locks in fire alarm event (2)- Remote AR-727-CM-IO CH1/CH2 RS485 readers
Network server AR-727-CM-IO-0804M is built-in DI0 input that can be connected to fire alarm detector; all controllers connected under the same network can be released door locks via UDP broadcast method; the network controller can also be set to accept any or only one signal of network server to release door lock.
Introduction of releasing all door locks in fire alarm event (3)- CH1/CH2 RS485 Readers under AR-727-CM-IO
AR-727-CM-IO-0804M is built-in fire detection input (DI0); When the fire alarm is triggered, all door locks of CH1/CH2 RS-485 controllers under AR-727-CM-IO will be released for user to escape.
AR-727-CM-IO-0804M needs to enable the “Fire Alarm (DI0) Open Doors” function
(The function can be set on browser, default IP address is 192.168.1.127)
Introduction of releasing all door locks in fire alarm event (4) –Control CH1/CH2 RS485 Reader under Multi-door controller
SOYAL Multi-door controller AR-716-E16 and AR-716-E18 are built-in fire detection input. Only connect the input to fire detector central controller and then once the fire alarm is triggered, all door locks of RS-485 controllers under Multi-door control panel will be released for user to escape.