Serial NO. : H03513002-EN
Date of Editing : 2015-09-08
Questions : How to use SOYAL E/V5 Controller for Lift Control?
Problem Solving :
Suggestion: Upgrade one newer firmware after released date of 20150903
APS837E____V0304 150903.STM & After
APS829Ev5__V0304 150903.STM & After
APS727Ev5__V0304 150903.STM & After
◎ Total 3 methods while using E/V5 Controller for Lift Control
Method1: Change Built-in Host Port for PC communication to Lift Control
1-1: Wiring
1-2: Enable Lift Control Setting
1-2-1 Way1 via Software : Change RS485-1 Option from Default Host Comm. Port to Lift Controller
※ RS485-1 port could not set the same Lift Controller option with RS485-3 at the same time that will cause output conflict ; please Change RS485-3 port from Lift Controller (default) to other Output option ….(reserved) or LED Panel or upgrade firmware V0304 150903.STM & After to solve the conflict
1-2-2 via Hardware:
1. Enter Programming Mode ( *PPPPPP#, P= Master Code, default 123456)
2. 5. Tools -----> 4. Terminal Port ------> Change Default 1: Host to 0: Lift; Select Baud 0: 9600(default)
3. 5. Tools ----->0. UART Port ------> Change Default 0: OEM-960 to other setting 1: SIM or 2: LED
Method2 : Connect 5V TTL/485 Converter AR-725L485 from TTL Port CN11 to AR-401RO16B
2-1. Wiring as below ※ TTL cable of AR-725L485(DC 5V) is not allowed to extend
2-2: Enable Lift Control Setting
2-2-1. Way1 via Software :
※ RS485-2 port could not set the same Lift Controller option with RS485-3 at the same time that will cause output conflict ; please Change RS485-3 port from Lift Controller (default) to other Output option ….(reserved) or LED Panel or upgrade firmware V0304 150903.STM & After to solve the conflict
2-2-2 Way2 via Hardware:
1. Enter Programming Mode ( *PPPPPP#, P= Master Code, default 123456)
2. 5. Tools -----> 5. Ext. Comm Port ------> Select 1: Lift(default) ------> Select Baud 0: 9600(default)
※ For RS485-2 Port , Both Baud Rate 4800 and 9600 can be used for lift control
If Baud Rate of 401RO16B is 9600, please adjust controller with same Baud Rate 1: 9600
If Baud Rate of 401RO16B is 4800, please adjust controller with same Baud Rate 0: 4800
3. 5. Tools ----->0. UART Port ------> Change Default 0: OEM-960 to other setting 1: SIM or 2: LED
Method3 : Connect 5V TTL/485 Converter AR-725L485 from TTL Port CN9 to AR-401RO16B
3-1. Wiring as below ※ TTL cable of AR-725L485(DC 5V) is not allowed to extend
3-2: Enable Lift Control Setting
3-2-1. Way1 via Software :
※ RS485-2 port could not set the same Lift Controller option with RS485-3 at the same time that will cause output conflict ; please Change RS485-2 port from Lift Controller (default) to other Output option Line Panel or upgrade firmware V0304 150903.STM & After to solve the conflict
(5) Click “ Write” to write new parameter setting to controller
3-2-2. Way2 via Hardware:
1. Enter Programming Mode ( *PPPPPP#, P= Master Code, default 123456)
2. 5. Tools ----->0. UART Port ------>Select 0: OEM-960 (lift Control) default
3. 5. Tools -----> 5. Ext. Comm Port ------>Change default 1:Lift to 0: Suspend or 3. PRN
◎ Total 2 way to edit the floor card for User
1. Way1 :Setting via 701Client Software
(1) Click [8-User] setting icon on Menu Bar
(2) Select [Tools]------> [User Access Floor Edit]
(3) Select[User Address]
(4) Tick [Floor Number] the use allow to access
(5) Select [829E/727H/725H]
(6) Select [Node ID]
(7) Select as Mode Type
(8) Click [Write Current] to write the user floor data to controller
※ If need to download all user floor cards setting at one time , please click [Save] to save current data ,after completing all setting, click [Write All] to download all.
※ If want to check the user current data, please ,click [Read Current] to read data from controller
※ If want to check all user data, please ,click [Read All] to read all data from controller
2. Way2 :Setting via Hardware