Questions : Connecting Multi-Door Controller 716-E16 with Access Reader and setting up Alarm after door opening for more than 30 seconds
Problem Solving :
Wiring Diagram
On CN10 Door Sensor will connect to SEN if using PORT 1
On CN13 Door Sensor will connect to SEN if using PORT 0
On CN6 COM connect to Power, ALARM connect to Alarm
Enabling Arming Mode
Step 1. Enter Master Code
Step 2. Enter **#
On Event Log you will see
To Disarming, you only need to Enter Master Code
Step 1. Click [G Reader Status Monitor]
Step 2. Select Controller Node ID (if only one multi-door controller 721E-v2, select 001)
Select Reader Node ID, WG1 for port 0, WG2 for port 1
Step 3. Click [Read Status]
Step 4. Click [V Arming]
Step 5. Arming status will be Arming mode
Step 6. To Disarming, click [X Disarm], the Arming status will be Disarm
701 SERVER setting
Step 1. Select picture [881EF/V_725Ev2 Parameter]
Step 2. Select Target Node
Step 3. Click [Read]
Step 4. DOOR RELAY (PORT 0) / RELAY[WG](PORT1) 7 seconds (recommendation) à must enter the door before 7 seconds, otherwise the door will be locked again
Step 5. OPEN TOO LONG (PORT0) / TOO LONG [WG] (PORT1) 23 seconds à opening door too long
RELAY+TOO LONG = after how many seconds it will activate alarm
in this case, RELAY 30 seconds after swiping the card to activate the siren
Step 6. ALARM RELAY You can select how long the siren will keep beeping until it stops
i.e 10 seconds, the siren will stop beeping after 10 seconds
Step 7. Select [WRITE] to apply changes
Here is what will show on Event Log
SETTING FOR PORT 0 SETTING FOR PORT 1