Serial NO. : H00110001-EN
Date of Editing :
Questions : How to set up floor control on AR-721H and how to connect it?
Problem Solving :
1. Function setting:
After enter edit mode, input command 2 4 * 0 0 2 # to set up
[Alarm output] as [Series output].
2. Wiring:
Connector P1 Grey wire【Series output】 to AR-829L485 yellow wire. You should supply the controller and AR-829L485 with the same power.
3. Single-floor setting:
2 7 * 0 0 0 0 1 * 3 1 #
User Address Floor
Multi-floor setting:
User Address Group Floor setting
Floor setting definition
0: Enable floor
1: Disable floor
According to the following table, this user can reach floor 8/ 7/ 2/ 1
※Input 2 3 * to change AR-401RO16 relay time, which will provide enough time for user to press floor button in the elevator. Please refer 401RO16 user manual for detailed information.