Questions : How to copy/replicate user card data from one H Series controller to the other H Series controllers?
Problem Solving :
Compatibility tools table:
Mode | M4/M8 | M6 |
Tool | 701ClientSQL | ISP Tool |
Communication | 1. TCP/IP (converter AR-727-CM) 2. RS485(converter AR-321CM) | RS485(converter AR-321CM) |
*Entering program mode will sounds different beeps to identify the modes (M4:4 beeps / M6:6 beeps / M8:8 beeps)
Connection:
The connection method please refer to the manual of 701ServerSQL, paragraph 6.2 >> Link
701ClientSQL operation introduction:
*It is required to duplicate the file of default.usr in 701Client folder, preventing from the user data be covered.
*Read and write card data is different in step5 only.
Read / Write card data methods:
Step1. 701ClientSQL > 8.User Card Data
Step2. Select tools > Read / Write to Cxx
Step3. Select area, controller node ID
--read card data from controller of node ID 001 for instance
--write card data from controller of node ID 002 for instance
Step4. Select “Write” or “Read” and card range
Step5. Select the controller configuration
Step6. press “start”
ISP Tool Operation Introduction:
Step1. Turn off 701ClientSQL、701ServerSQL
Step2. Execute ISP Tools
2-1 select COM port
2-2 select controller model
2-3 select the node ID of controller
2-4 select “Read EEPROM User”
2-5 the progress bar will display the progress percent
2-6 save the data as .EEP file
Step3.connect second controller
3-1 select COM port
3-2 select controller model
3-3 select the node ID of controller
3-4 select “Write EEPROM User”
3-5 select the .EEP file
3-6 the progress bar will display the progress percent