Hardware Features:
Logic Programming Features:
Programming User Interface:
Built-in easy to program and interactive user interface
Case Introduction :
1. Index 063 (Seconds) Timer: Set the timer for 60 seconds. The condition TMR:000 LESS:060 indicates that the timer for the 000 group cycles between 0 and 60 seconds.
2. Index 061 (Minutes) CNT Inc (Out# 001): Set the timer for minutes. The condition TMR:000 EQUA:060 indicates that when the timer for the 000 group reaches 60 seconds, the CNT Inc (Out# 001) will increase by 1, representing 1 minute.
3.Index 062 CNT Rst (Out# 001): Set the reset for minutes. The condition CNT:001 MORE:059 indicates that the CNT for the 001 group will reset to 0 as long as it's greater than 59.
4.Index 059 (Hours) CNT Inc (Out# 002): Set the timer for hours. The condition CNT:001 EQUA:060 indicates that when the CNT for the 001 group reaches 60 minutes, the CNT Inc (Out# 002) will increase by 1, representing 1 hour. Index 060 CNT Rst (Out# 002): Set the reset for hours. The condition CNT:002 EQUA:024 indicates that the CNT for the 002 group will reset to 0 when it equals 24.
5.Index 058 (Pulse 007): Set the output to pulse for 10 seconds every minute. The condition is TIMER for the 000 group equals 0. This occurs because the Timer cycles within the range of 0 to 60 seconds, causing a 10-second activation at the beginning of each minute.
6. Index 056/57 (Cycle 006): Set the cycle output to trigger every day at 18:00, with a 0.3-second on/off unit, continuing until 18:30 in the evening.