Conditions:
4 Doors Interlock: When one of the doors is unlocked, other 3 doors could not be unlocked until that door is closed
Feature:
Contact Description:
Door | DI Address PB | DI Address Door Sensor | DO Address Door Relay | DO Address Alarm |
Door A | DIX0 | DIX1 | DOY0 | DOY1 |
Door B | DIX2 | DIX3 | DOY2 | DOY3 |
Door C | DIX4 | DIX5 | DOY4 | DOY5 |
Door D | DIX6 | DIX7 | DOY6 | DOY7 |
Fire DI | DIX16 |
Case Explanation :
We will use Door A as example to explain the program logic:
1. When the door sensor DIX3/DX5/DIX7 and the door lock relay DOY2/DOY4/DOY6 of door B/door C/door D are closed, press Door A push button DIX0 , the door lock relay DOY0 can be trigger on 6 seconds.
2. When the fire alarm input DIX16 is closed, the door lock relay of door A/door B/door C/door D can be released on;
3. When the door sensor DIX1 of door A is closed, the door lock relay of door A can be automatically relocked;
4. When the door sensor DIX1 of door A is forced to open and the door relay DOY0 of door A is off, the alarm relay DOY1 of door A will be turned on;
5. When the door sensor DIX1 of door A is open, the timer TMR0 is triggered. When TMR0 is more than 8 seconds, the door open too long alarm relay DOY1 is triggered.
6. When the door sensor DIX1 of door A is closed, the alarm relay DOY1 can be stopped.
WEB Setting:
Ladder Programming: