[ WEB PLC ] 4 Doors Interlock

Conditions:

4 Doors Interlock: When one of the doors is unlocked, other 3 doors could not be unlocked until that door is closed

Feature:

  • Door Relay time 6 Secs
  • Auto Relock
  • Open Too Long Alarm 8 Secs
  • Force Open Alarm
  • Stop Alarm by Close Door
  • Fire Alarm Trigger All Doors

 

Contact Description:

DoorDI Address
PB
DI Address
Door Sensor
DO Address
Door Relay
DO Address
Alarm

Door A

DIX0DIX1DOY0DOY1

Door B

DIX2DIX3DOY2DOY3

Door C

DIX4DIX5DOY4DOY5

Door D

DIX6DIX7DOY6DOY7
Fire DIDIX16   

 

Case Explanation : 

We will use Door A as example to explain the program logic:

1. When the door sensor DIX3/DX5/DIX7 and the door lock relay DOY2/DOY4/DOY6 of door B/door C/door D are closed, press Door A push button DIX0 , the door lock relay DOY0 can be trigger on 6 seconds.

2. When the fire alarm input DIX16 is closed, the door lock relay of door A/door B/door C/door D can be released on;

3. When the door sensor DIX1 of door A is closed, the door lock relay of door A can be automatically relocked;

4. When the door sensor DIX1 of door A is forced to open and the door relay DOY0 of door A is off, the alarm relay DOY1 of door A will be turned on;

5. When the door sensor DIX1 of door A is open, the timer TMR0 is triggered. When TMR0 is more than 8 seconds, the door open too long alarm relay DOY1 is triggered.

6. When the door sensor DIX1 of door A is closed, the alarm relay DOY1 can be stopped.

 

WEB Setting:

Ladder Programming:

  • X0/X1/…/Xn represent actual input DIX0/DIX1/…/DIXn
  • Y0/Y1/…/Yn represent actual output DOY0/DOY1/…/DOYn
  • M0/M1/…/Mn represent virtual output DOM0/DOM1/…/DOMn


 