How to set up magnetic contact and door relay time on 7 series controller?
2021-06-16
No. H00106003-EN

Serial NO. : H00106003-EN

Date of Editing : 

Questions :  How to set up magnetic contact and door relay time on 7 series controller?

Problem Solving :

 

Please follow the procedures below to set up alarm output and door relay time.

1. Enter edit mode *123456#

    Command 03*TTT#→TTT : Alarm relay time

    Command 18*TTT#→TTT : door close time. (Default value: 15 seconds)

    Command 28*NNN#→Force open alarm setting.

                                            128: Enable

                                            000: Disable

 

2. Press 【*】【*】【#】to exit edit mode and enter ARMING mode.

 

03*000# explanation:

When you set up alarm relay time as 000, relay will switch to another mode. Which means when relay is off, after present the valid card, relay will switch to on; When relay is on, after present the valid card, relay will switch to off.