Configure Antipass-back of Onboard wiegand ports Multi-door Network Controller (AR-716-E18)
2020-12-25
No. H01611001-EN

Serial NO.:  H01611001-EN

Date of Editing: 2019-06-03

Answer:

Index:

(一) Controller Configuration for Ingress and Egress

(二) Personnel Configuration for Ingress and Egress

(三) Checklist for Inspection

 

Enabling the one-in-one-out feature requires the following two main elements:

1.The access control device must be enabled with the one-in-one-out feature and configured for the entry and exit doors.

2.The user card must be enabled with the one-in-one-out feature.

 

(一) Controller Configuration for Ingress and Egress 

To integrate the different unique root readers with the SOYAL system, both AR-716-E16 and AR-716-E18 are equipped with two WG ports.

The unique root reader connected to WG Port1 has a fixed station number of 17. However, the unique root reader connected to WG Port 2 has a fixed station number of 18.

  • When applied in a one-in-one-out access control scenario, the unique root reader with station number 17 is designated for the "Entry Door," while the unique root reader with station number 18 is designated for the "Exit Door." 

To ensure these two unique root readers coordinate effectively for one-in-one-out control, in addition to setting the door numbers in 701ServerSQL, the "Antipass-back IN Door" and "Antipass-back OUT Door" options must be selected.

 

(二) Personnel Configuration for Ingress and Egress 

Step 1. In 701ClientSQL, select Card Data Editing for Card 8.

Step 2. When entering the personnel card data, make sure to check the "Ingress and Egress" option.

Step 3. Click on Save and Generate Download Data File.

Step 4. Finally, click on Download for this specific card.

Step 5. Swipe the card for verification as shown in the diagram:

 

(三) Checklist for Inspection 

FieldItemCheck Content
1.

Confirm correct wiring between multiple controllers and readers. (To prevent equipment damage, please cut or isolate unused wires and avoid twisting them together directly.)

2.

Check if the door number assignment is selected for the multiple controllers.

3.

Verify if the "Ingress and Egress" feature is checked in the 701ClientSQL personnel card data editing.

4.

Ensure that the settings are downloaded and written to the controller.